The S&L Catalog
Green Light Express Dimming and Switching Panels
Model: GLPX
- Crestron Green Light Express® panels for 120- or 277-Volt dimming and switching
- 8 to 56 circuits per panel
- Feed-through type panels
- Field-replaceable lighting modules
- Models with separate installations for the rough-in enclosure and the lay-in panel available
Crestron Green Light Express® is a low-cost collection of dimming and switching panels with a feed-through wiring configuration. These efficient lighting control panels are designed for use in office buildings, warehouses, parking garages, sports facilities, public spaces, and anywhere centralized dimming or switching is required. With a smaller form factor than the Crestron Green Light® Series, the Green Light Express Series is the economical solution for reliable lighting control. An extensive selection of Crestron keypads, touch screens, occupancy sensors, photosensors, shade controllers, and numerous other peripheral options afford astounding design flexibility with unparalleled capability for integration.
GLPX-MM Two-Stage Installation models afford peace-of-mind. In two-stage installations, the rough-in enclosure is ordered and installed months in advance of the lay-in panel, allowing time for prewiring and rough-in work. The lay-in panel is ordered separately and delivered with all of the equipment it houses already in place. Simply lay the panel in to the previously installed enclosure to complete the installation. This installation method ensures that delicate equipment is not disturbed or damaged during construction and pre-wiring.
- Crestron Green Light Express® panels for 120- or 277-Volt dimming and switching
- 8 to 56 circuits per panel
- Feed-through type panels
- Field-replaceable lighting modules
- Models with separate installations for the rough-in enclosure and the lay-in panel available
- Factory assembled and tested
- Up to 8, 24, 56, or 84 relays max per panel
- UL924 listed (emergency power equipment)
- Spec Sheet available - Yes
- Operating Temperature (Maximum): 104 F
- Operating Temperature (Minimum): 32 F
- Regulatory Compliance: UL Listed, FCC Part 15
- Certifications: UL, CE, FCC
- Load Ratings:
- Switching (GLPX-SW)
- Switch Channels: 8 to 56 depending upon panel size and options, each channel phase independent
- Per Channel: 16 Amps at100 to 277 Volts AC, 50/60 Hz;
0.5 HP at 120 Volts, 1 HP at 230 Volts, 1 HP at 277 Volts - Load Types: Incandescent, magnetic low-voltage, electronic low-voltage, neon/cold cathode, fluorescent ballast, high-intensity discharge, LED, motor
- High-Inrush Switching (GLPX-HSW)
- Switch Channels: 8 to 32 depending upon panel size and options, each channel phase independent
- Per Channel: 16 Amps at 100 to 277 Volts AC, 50/60 Hz;
0.5 HP at 120 Volts, 1 HP at 230 Volts, 1 HP at 277 Volts - Load Types: Incandescent, magnetic low-voltage, electronic low-voltage, neon/cold cathode, fluorescent ballast, high-intensity discharge, LED, motor
- Relay Lifetime: 1,000,000 on/off operations at full electronic ballast load
- Heavy-Duty Switching (GLPX-HDSW)
- Switch Channels: 8 to 56 single-pole, 4 to 28 double-pole, depending upon panel size and options, each channel phase independent
- Per Channel (Single Pole Relay): 20 Amps at 120-347 Volts AC;
0.5 HP at 125 Volts AC, 1.5 HP at 220-277 Volts AC - Per Channel (Double Pole Relay): 20 Amps at 120-480 Volts AC;
0.5 HP at 125 Volts AC, 1.5 HP at 220-277 Volts AC - Load Types: Incandescent, magnetic low-voltage, electronic low-voltage, neon/cold cathode, fluorescent ballast, high-intensity discharge, LED, motor, electronic ballast
- Relay Lifetime: 30,000 or more on/off operations at full load
- Dimming (GLPX-2DIM8)
- Dim Channels: 8 to 24, depending upon panel size and options
- Per Feed: 16 Amps at 100 to 277 Volts AC, 50/60 Hz;Feeds 4 channels
- Dim Load Types: Incandescent, magnetic low-voltage, neon/cold cathode, 2-wire fluorescent ballast, 3-wire fluorescent ballast, LED
- Switch Load Types: Incandescent, magnetic low-voltage, electronic low-voltage, neon/cold cathode, fluorescent ballast, high-intensity discharge, LED
- Lighting Protection :
- Can withstand 6 kV / 3 kA surge, as per IEC 61000-4-5 and ANSI/IEEE C62.41-1991
- Enclosure:
- NEMA Type 1, IP20 rated protection, for indoor use only; 16-gauge galvanized steel, surface wall mount; Gray front cover with powder coated finish
- Enclosure Dimensions:
- GLEX-FT-8
- Height: 12-5/16 in (313mm)
- Width: 14-1/8 in (359 mm)
- Depth: 4-3/8 in (111 mm)
- GLEX-FT-24 & GLEX-FT-24-MMOE
- Height: 24-1/4 in (616 mm)
- Width: 16-1/8 in (409 mm)
- Depth: 4-7/16 in (113 mm)
- GLEX-FT-56&GLEX-FT-56-MMOE
- Height: 39-21/32 in (1007 mm)
- Width: 16-1/8 in (409 mm)
- Depth: 4-7/16 in (113 mm)
- GLEX-FT-84-HC& GLEX-FT-84-MMOE
- Height: 63 in (1600 mm)
- Width: 15-1/4 in (388 mm)
- Depth: 4-1/2 in (115 mm)
- GLEX-FT-8
- WEIGHT:
- GLEX-FT-8: 10.4 lbs (4.70 kg)
- GLEX-FT-24&GLEX-FT-24-MMOE: 19.0 lbs (8.61 kg)
- GLEX-FT-24-MMP: 6.0 lbs (2.72 kg)
- GLEX-FT-56&GLEX-FT-56-MMOE: 28.0 lbs (12.68 kg)
- GLEX-FT-56-MMP: 10.5 lbs (4.76 kg)
- GLEX-FT-84-HC&GLEX-FT-84-MMOE: 42.0 lbs (19.03 kg)
- GLEX-FT-84-MMP: 11.0 lbs (5.00 kg)
- Humidity: 10 to 90 % RH (non-condensing)
S&L Integrated
7 Midway Road
Thomasville, GA 31757
USA
(229) 378-8866
https://slintegrated.com/